Features:
The Class 47
Alternator Is Of Industrial Design Specifically
For Use In Pump
and Compressor Applications. It Is Easily
Field Installed
and Wired In Control Panels, Pump Panels
Or As A
Separately Enclosed Unit For Surface Mounting.
Volts Make Break
The Alternator
Has Single Pole Double Throw Heavy Duty
10 Ampere Silver
Cadmium Oxide Contacts Enclosed In A
Transparent Dust
Cover. The Snap Action Contacts Transfer
When The Unit Is
De-Energized. The Circuit Is Never Closed
Or Opened While
Current Is Being Conducted. This Provides
Increased
Control Life. The Alternator Is Wired To Operate
The Second Motor
Starter The Next Time A Pump Operation
Is Required.
Coil Data:
|
Watts |
Volts
60
Hz |
Inrush
Open
Magnet |
Normal
Sealed
Magnet |
|
Amps |
VA |
Amps |
VA |
| |
24 |
4.0 |
|
0.629 |
|
| |
120 |
0.8 |
|
0.126 |
|
| 4 |
240 |
0.4 |
96 |
0.063 |
15.1 |
| |
480 |
0.2 |
|
0.031 |
|
|
Application:
The Alternator
Relay Provides A Means Of Automatically
Alternating The
Operation Of Two Separately Mounted
Motor Driven
Pumps Or Compressors. This Alternating
Action Assures
Even Readiness and Wear On Both Pumps.+
Electrical Ratings:
NEMA AC Ratings 50/60 Hz
NEMA A600 10 Continuous Amps
Wiring Diagrams
(Typical):
Alternating
Alternating & Duplexing

For Added
Safety, Replace The Single Pole Float Switch (B)
With A 2 Pole
Auxiliary (B1) Float Switch (See Dotted Wiring).
Switch (A) Is Set To Close
Before Switch (B).
|